EasyManuals Logo

BONFIGLIOLI active User Manual

BONFIGLIOLI active
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
06/0542
42 06/05
Control word State word
Bit No. Name Bit No. Name
0 S1IND / FUF 0 Ready to switch on
1 S2IND 1 Ready
2 S3IND 2 Operation enabled
3 S4IND 3 Fault
4 S5IND 4
V
olta
g
e-inhibit
5 S6IND 5 Quick stop
6 S7IND 6 Switch on inhibit
7 S8IND 7 Warning
8 - 8 -
9 - 9 Remote
10 - 10 Reference value reached
11 - 11 Limit value reached
12 - 12 -
13 - 13 -
14 - 14 -
15 - 15 Warning 2
State word
State HEX (*) Bit 6 Bit 5 Bit 3 Bit 2 Bit 1 Bit 0
Ready 0x23 0 1 0 0 1 1
Operation enabled 0x27 0 1 0 1 1 1
Fault 0x08 0 x 1 0 0 0
(*) without considering bits 7 to bit 15
Note: A fault occurring leads to a switch-over to the "Fault" state.
A fault can only be acknowled
g
ed 15 seconds after the occurrence of the
fault, as a blocking time is active internally.
The Warning bit "Bit No. 7" can be set at any time. It displays an device-internal
warning message. The evaluation of the warnin
g
available is done by readin
g
out the
warning status with the parameter
Warnings 270.
The Remote bit "Bit No. 9" is set if the operation mode control via remote contacts
(
Local/Remote 412 = 2) has been set and the hardware release is available (S1IND
= 1). Only then can the frequency inverter be controlled via the control word.
The bit Reference value reached "Bit No. 10" is set when the reference value
specified has been reached. In the special case of power failure regulation, the bit is
also set if the power failure re
gulation has reached the frequency 0 Hz (see operating
instructions). For "Reference value reached“ there is a hysteresis (tolerance ran
g
e),
which can be set via the parameter
max. Control deviation 549 (see operatin
g
instructions).
The bit Limit value active "Bit No. 11" displays that an internal limit is active. This
can, for example, be the present current limit, the torque limit or the overvoltage
limit. All the functions lead to the reference value being quit or not reached.
The bit Warning 2 "Bit No. 15" reports a warning which leads to a fault switch-of
f
of the frequency inverter within a short time. This bit is set if there is a warnin
g
for
motor temperature, heat sink/inside temperature, Ixt monitoring or mains phase
failure.

Table of Contents

Other manuals for BONFIGLIOLI active

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI active and is the answer not in the manual?

BONFIGLIOLI active Specifications

General IconGeneral
BrandBONFIGLIOLI
Modelactive
CategoryDC Drives
LanguageEnglish

Related product manuals