CC488 | Quick Reference Guide | 2.0 Programming Parameters EN | 18
Bosch Security Systems | 6/04 | 4998152446B
2.13.3 Polarity (Modes)
Option Description
0 Disabled
1 Normally open, going low
2 Normally open, pulsing low
3 Normally open, one shot low
4 Normally open, one shot low (reset)
5 Normally open, one shot low (re-trigger)
6 Normally open, latching low
7 Reserved
8 Normally low, going open
9 Normally low, pulsing open
10 Normally low, one shot open
11 Normally low, one shot open (reset)
12 Normally low, one shot open (re-trigger)
13 Normally low, latching open
2.13.4 Time Base
Option Description
1 200 ms
2 1 sec.
3 1 min.
4 1 hr.
2.13.5 Time Base Multiplier
Enter a value between 01 and 99.
2.13.6 One Shot Mode
When you program the output polarity as one
shot, the time base is multiplied by the time base
multiplier. (For example, if the time base = 2 and
the multiplier = 05, the output operates for 10 sec.)
2.13.7 Pulsing Mode
When you program the output polarity as pulsing,
the time base becomes the ON time and the
multiplier becomes the OFF time. The OFF time is
the time base x the multiplier. (For example, if you
want the output to pulse 1 sec. ON and 5 sec.
OFF, you would program time base as one and the
multiplier as five.)
2.14 Time Programming
2.14.1 Entry Time 1
Location
410 to 411
Location Default
Increments of 1 sec. (0 to 15 sec.) 410 4
Increments of 16 sec. (0 to 240 sec.) 411 1
2.14.2 Entry Time 2
Location
412 to 413
Location Default
Increments of 1 sec. (0 to 15 sec.) 412 8
Increments of 16 sec. (0 to 240 sec.) 413 2
2.14.3 Exit Time (AWAY/STAY Modes)
Location
414 to 415
Location Default
Increments of 1 sec. (0 to 15 sec.) 414 12
Increments of 16 sec. (0 to 240 sec.) 415 3
2.14.4 Entry Guard Time For STAY Mode
Location
416 to 417
Location Default
Increments of 1 sec. (0 to 15 sec.) 416 0
Increments of 16 sec. (0 to 240 sec.) 417 0
2.14.5 Delay Alarm Report Time
Location
418 to 419
Location Default
Increments of 1 sec. (0 to 15 sec.) 418 0
Increments of 16 sec. (0 to 240 sec.) 419 0
2.14.6 Sensor Watch Time
Location
420 to 421
Location Default
Increments of days (tens digit) 420 0
Increments of days (units digit) 421 0
2.14.7 Codepad Lockout Time
Location
422
Default
0
Increments of 10 sec. (0 sec. to 150 sec.)
2.14.8 Siren Run Time
Location
423
Default
5
Increments of 1 min. (0 min. to 15 min.)
2.14.9 Siren Sound Rate
Location
424
Default
7
0 = Slowest frequency
15 = Fastest frequency
2.14.10 Auto Arming Pre-Alert Time
Location
425
Default
1
Increments of 5 min. (0 min. to 75 min.)
2.14.11 Auto Arming Time
Location
426 to 429
Location Default
Hour of the day (tens digit) 426 0
Hour of the day (units digit) 427 0
Minute of the day (tens digit) 428 0
Minute of the day (units digit) 429 0
2.14.12 Auto Disarming Time
Location
430 to 433
Location Default
Hour of the day (tens digit) 430 0
Hour of the day (units digit) 431 0
Minute of the day (tens digit) 432 0
Minute of the day (units digit) 433 0
2.14.13 Kiss-Off Wait Time
Location
434
Default
3
Increments of 500 ms (500 ms = 8 sec.)