Flexible Automation
Installation
6-6
1070 072 143-101
6.4 Power input from 24 V power supply
Module Power input
Fan unit with 3 fans 1.0 A
Fan unit with 2 fans 0.8 A
Fan unit K with 1 fan 0.6 A
Power supply module NT24 6.9 A, making current 18 A
Input module E 24 V-, 95 inputs 4 mA per input set + external load
Input modules E 24 V- 15 mA per input set
+ external load
E analog 300 mA
E 10 ana 170 mA
IE 24 V- 100 mA
Output modules
1070 048 483, 1070 075 333
1070 048 485, 1070 075 337
1070 041 348, 1070 044 305
40 mA +15 mA per output set +
external load
Output module 1070 050 634 36 mA +8 mA per output set +
external load
Output modules,
1070 047 964, 1070 050 560
70 mA +8 mA per output set +
external load
Output modules,
1070 044 834, 1070 075 340
40 mA +16 mA per output set
A analog 300 mA
A 10 ana 700 mA
BTN DESI 65KDP 250 mA + external load
VTSE 420 mA, + power input of the
valves
RM4DP 1.35 A
Counter module EZ50 250 mA
Positioning module CC10 1.45 A
Temperature controller module
RT6
250 mA + external load
Power source module SQ16 250 mA
Peripheral coupling module PBK power input of the channel mod
ules
Channel module MOBY ® I/F 400 mA
Fig. 6-7 Power input from 24 V power supply