1.4 General specifications
. The data given regarding operation conditions apply to operation with
out a memory card. The operation conditions of the manufacturer must
also be observed when operating with a memory card.
Specifications
CL400
complies to standards D DIN EN 500812
D DIN EN 500822
D DIN EN 611312
D DIN EN 602041
D DIN VDE 0160
D DIN VDE 04701
Power supply D NT1, NT2, NT3
220/230 V (-15%, +10%)
110/115 V (-15%, +10%)
D NT24
24 V (-33%, +71%)
Interference immunity built into the
subrack
D High-frequency electromag
netic fields to DIN EN 611312
Test bay strength 10 V/m
Frequency band 27 to 500 MHz
Sweep rate 0.0015 Dek./s
D electrostatic discharge to tan
gible housing parts to
EN 500822
D ESD resistance 4 for humidity
class RH2
D Test voltage
Air discharge 15 kV
Contact discharge 8 kV
D mains-borne disturbances
D rapid burst pulse, sym. 2 kV
to IEC 8014
D 2 kV for power supply module
and digital inputs/outputs
D 1 kV for analog inputs/outputs,
serial interfaces and interrupt in
puts
D dampened sine 1 MHz,
sym. 1 kV to IEC 2554
1 kV for power supply module and
digital inputs/outputs