D7212GV3 | Program Entry Guide | 6.0 AUXPARM EN | 125
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Passcode Length
Default: 0
Selection:
0, 3, 4, 5, or 6
0 Sets a variable length for user
passcodes, allowing for backward
compatibility.
3, 4, 5, or 6 Sets a fixed length to all user
passcodes.
During entry delay, the code is accepted when the
last digit is pressed to disarm the area.
For SIA CP-01 Compliance:
Passcode Length must be set to 3, 4, 5, or 6.
Swinger Count
Default: 1
Selection:
1, 2, 3, or 4
1, 2 Number of fault or trouble bypasses
allowed per hour for SIA CP-01
compliance.
3 Optional fault count
4 Value used for backward
compatibility with previous control
panel operation.
When a point has P# Swinger Bypass set to Yes,
the value set in Swinger Count determines the
number of times the point is faulted erroneously
within an hour before it is automatically bypassed.
For SIA CP-01 Compliance:
P## Swinger Bypass can be Yes or No.
If P## Swinger Bypass is Yes, Swinger
Count must be 1 or 2.
Remote Warning
Default: Yes
Selection:
Yes or No
Yes The system uses the Alarm Bell
output to annunciate the arming and
disarming of an area through remote
software, or a remote arming device
such as a key switch or key fob.
No No remote warning occurs to
annunciate the arming and disarming
of an area through remote software,
or a remote arming device such as a
key switch or key fob.
Upon remote arming, the output pulses on for 2 sec.
Upon remote disarming, the output pulses on, off, on,
off for 2 sec each.
For SIA CP-01 Compliance
Remote Warning must be set to Yes.
Crystal Time Adjust
Default: No
Selection:
Yes or No
Yes Set the clock time control on the
control panel to the on-board crystal
frequency.
No Do not set the clock time control on
the control panel to the on-board
crystal frequency.
When set to Yes, the control panel switches its clock
time control from the traditional AC frequency to the
on-board crystal frequency.