D7212GV3 | Program Entry Guide | 7.0 SIA CP-01 Quick Reference EN | 128
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
7.0 SIA CP-01 Quick Reference
Table 35: Programming the Control Panels for SIA CP--01 Compliance
Prompt Name
Bosch Recommended Settings
for SIA CP-01 Compliance
Shipping Default References
Phone #
(Prefix backup phone number with
Call Waiting disable command)
{Blank} Page 8
Duress Type Option 3 0 (disabled) Page 30
Cancel Report Yes Yes Page 31
A# Exit Dly Time 45 sec to 255 sec 60 sec Page 32
A# Duress Enable Yes No Page 33
A# Exit Restart Yes or No Yes Page 43
A# Arm No Exit Yes or No Yes Page 43
A# Two Man Rule No No Page 41
A# Early Ambush No No Page 42
A# Exit Warning Yes Yes Page 43
A# Entry Warning Yes Yes Page 44
A# Burg Time
1
6 min to 90 min 6 min Page 36
A# Alarm Bell 1 to 128(64), A, B, C A (on-board alarm output) Page 70
CC# Entry Tone Yes or No Yes Page 48
CC# Exit Tone Yes or No Yes Page 49
CC# Abort Display Yes or No Yes Page 50
CC# Cancel Display Yes or No Yes Page 50
Master Arm Inst {Blank} {Blank} Page 55
Perimeter Instant {Blank} {Blank} Page 55
L## Send Duress [Blank] or E E
2
Page 68
L## Disarm [Blank] or E E
2
Page 61
L## Passcode Disarm [Blank] or E E
2
Page 68
P## Entry Delay 30 sec to 240 sec 30 sec Page 83
P## Alarm Abort Yes or No Yes
3
Page 90
Abort Window 15 sec to 45 sec 30 sec Page 124
Passcode Length 3 to 6 digits Disabled Page 125
Swinger Count 1 to 2 trips 1 trip Page 125
Remote Warning Yes Yes Page 125
Cross Point Time 5 to 255 sec 20 sec Page 127
P## Cross Point Yes or No No Page 89
1 The SIA allowed range is 1 min to 90 min. Must additionally comply with UL requirements, refer to section A# Burg Time.
2 L14 is the default duress user index.
3 The default for P## Alarm Abort is No for P3, P4, P5, and P22.