D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 16
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Refer to Section 6.6 Programming Path Numbers and
IP Addresses for Enhanced Communications on
page 117 to enable enhanced communication paths.
Keypad Programming of R# Backup Device
D1255
1. Refer to Figure 1 on page 6 to access Keypad
Programming and navigate to the
ROUTE GRP 1 - 4 option.
2. At the ROUTE GRP 1 - 4 prompt, enter the route
group number you wish to configure and press
[ENT]. The keypad reads RT GRP 1 PRIMARY,
and then the current configuration (for example,
SDI 88 PATH 4).
3. Press [NEXT] to advance to the RT GRP 1
BACKUP option. The Primary device cannot be
set to No Device before setting the Backup
Destination.
4. To change the configuration, press [ENT] when
the current configuration shows, and then press
[NEXT] or [PREV] to scroll through the options,
as listed in R# Backup Device on page 15.
5. When the keypad reads the desired configuration
option, press [ENT] to select it.
6. When the keypad reads Parameter Saved, your
selection has been configured.
D1260
1. Refer to Figure 2 on page 7 to access Keypad
Programming and navigate to the
Route Group 1 - 4 option.
2. At the Route Group 1 - 4 prompt, enter the route
group number you wish to configure and press
[ENT]. The keypad reads Rt Group 1 Primary,
and then the current configuration (for example,
SDI 88 PATH 4).
3. Press the Backup softkey. The keypad reads Rt
Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4). The
Primary device cannot be set to No Device
before setting the Backup Destination.
4. To change the configuration, press the Edit
softkey, and then press the Next or the Previous
softkey to scroll through the options, as listed in
R# Primary Device on page 14.
5. When the keypad reads the desired configuration
option, press the Save softkey to select it.
When the keypad reads Parameter Saved, your
selection has been configured.
2.3.9 Routing Group Categories
Fire Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 6: Fire Reports
Report
Selection
s
Report Description
R# Fire Alarm Yes, No Fire Event
R# Fire
Restore
(Alarm)
Yes, No
Fire restoral from
alarm
R# Fire
Missing
Yes, No Missing Fire point
R# Fire
Trouble
Yes, No Fire trouble
R# Fire
Supervis
Yes, No Fire supervision
R# Fire
Restore
(T/M/S)
Yes, No
Fire restoral from
trouble, missing, or
bypass
R# Fire
Cancel
Yes, No Canceled fire alarm
R# Fire Sup
Miss
Yes, No
Fire supervisory
missing
R# Fire Supv
Rest
Yes, No
Restorals from Fire
Supervision