D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 23
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Table 17: Event Descriptions, Priorities, and
Numbers, continued
Event Description
Event
Priority
Event
Number
Parameters Changed 008 054
RPS Access OK 008 064
RPS Access Fail 008 065
Remote Reset 008 079
Program Access OK n/a n/a
Program Access Fail n/a n/a
Service Start 008 029
Service End 008 030
Fire Walk Start 008 036
Fire Walk End 008 037
Walk Test Start 008 038
Walk Test End 008 039
Extra Point 008 023
Send Point Text n/a n/a
RF Low Battery 006 093
RF Battery Restore 006 094
Date Changed 008 059
Time Changed 008 060
Delete User 008 090
User Code Change 008 056
Area Watch 008 042
Card Assigned
1
008 110
Change Level
1
007 061
Access Granted
1
008 003
No Entry
1
008 115
Door Left Open
1
008 116
Cycle Door
1
008 112
Door Unlocked
1
008 113
Door Secure
1
008 114
Door Request
1
008 117
Door Locked
1
008 145
User Alarm COMMAND 7 002 005
User Alarm COMMAND 9 002 006
1
This event is not transmitted for the D7212GV3. Use
only the default setting.
2.4 Power Supervision
AC Fail Time
Default: 1:00
Selection:
0:01 to 90:00
Program the amount of time that AC power must be
off before the control panel responds to the AC
failure. The response to restoral of AC power is
delayed for the same amount of time. The control
panel always monitors AC. The response to this
prompt is the actuation of the relay programmed in
the Panel-Wide Relays prompt AC Failure (refer to
Section 2.12.2 Panel-Wide Relays on page 72) and
the AC Fail report enabled by the AC Fail/Restoral
Report prompt. Local annunciation of an AC failure is
controlled by the AC Fail Display prompt.
Resend AC Fail
Default: No Response
Selection:
No Response, 6 hrs, 12 Hrs
No
Response
Only send the AC Fail report upon
failure.
6 hr Send AC Fail report upon failure and
every 6 hours after this while the
failure persists.
12 hr Send AC Fail report upon failure and
every 12 hours after this while the
failure persists.
This prompt controls the repeated transmission of the
AC Failure report to the central station while the fault
persists. AC Fail/Restoral Report must be set to
Yes, and AC Tag Along must be set to No for this
feature to work.
To eliminate AC Reporting, AC Tag
Along and AC Fail/Restoral Report
must be programmed as No.
AC Fail Display
Default: 60 sec
Selection:
10 to 300 sec (in 5-sec
increments)
Program the length of time the AC power must be off
before the message SERVC AC FAIL shows on the
keypads. The response to restoral of AC power is
delayed for the same amount of time.