D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 25
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
2.5 Printer Parameters
One D9131A Parallel Printer Interface Modules can
be connected to the SDI bus in the D7212GV3. The
printer is identified by an address of 17. Options are
available for Routing Reports and area assignments.
Printer Address
Default: 17
Selection:
17
Enter the printer address you are programming.
P## Area Assign
Default: 1
Selection:
1 to 4
Assign an area to the printer programmed in Printer
Address.
P## Supervised
Default: No
Selection:
Yes or No
Yes Only one printer can be installed for
this P## SDI address.
No More than one unsupervised printer
can be installed using this P## SDI
address and the same address DIP
switch setting.
Supervise this SDI address. Generate Trouble SDI
## Reports and local trouble annunciation if a
problem occurs with this printer or the SDI bus.
Unsupervised printers sharing the same
address setting print the same text.
Trouble SDI ## Reports are always
reported as Area 1, Account 1 Events
regardless of where the SDI device is
assigned.
When P## Supervised is set to Yes and
all Printer Event Groups (such as P##
Fire Events, P## Burglar Event, or P##
Usr Chng Evt) are set to No, the control
panel does not generate Trouble SDI ##
Reports for the printer if the D9131A
becomes disconnected.
P## Scope
Default: No Printer
Selection:
No Printer, Area, Account, Panel
Wide, Custom
Panel
Wide
Printer prints all designated events
that occur panel-wide. A panel-wide
printer can cross account boundaries.
Account Printer prints all designated events
that occur within any area with the
same account number in which this
printer is assigned.
Area Printer prints all designated events
that occur in the area to which this
printer is assigned.
Custom Printer prints all events occurring in
areas programmed Yes for this
prompt regardless of any boundary
restrictions.
No Printer No printer installed at this address. If
a printer is connected, data does not
print.
P## A1 [through A4] in Scope
Default: No
Selection:
Yes or No
Yes Include Area # Events in the scope of
this printer.
No Does not include Area # Events in
the scope of this printer.
Only available if P## Scope is programmed Custom.
This program item determines if events occurring in
an area print at this printer.
Refer to the report tables in Section 2.3
Routing on page 12 to identify the events
that print. Events programmed as No in
Routing still print at the local printer.
Individual events within the report group
cannot be suppressed for events printed
at the local printer.
P## Fire Events
Default: Refer to the program record sheet
Selection:
Yes or No
Yes All events in this group print at
assigned printer.
No No events in this group print at
assigned printer.