D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 18
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Test Reports
Automatic: To send a single Test Report (R# Test
Report) automatically, enable Sked Function Code
#9 (Test Report) in the Skeds section of the program.
Refer to Table 9.
Manual: To send a single Test Report manually,
enter [COMMAND][4][3] at the keypad. Refer to the
Send Report prompt on page 57.
To expand this Test Report to include any off-normal
point condition or other off-normal system conditions,
Expand Test Report (refer to page 9) must be
programmed Yes. Refer to the footnotes with Table
10 on page 19 for a list of event types that are
included in an expanded test report. Additionally, the
expanded test report includes Summary Fire
Supervisory, Summary Fire Fault, Summary
Controlled Point Fault, and Summary Point Device
Fault conditions.
The control panel can generate an Expanded Off-
Normal Test Report by using Sked Function Code 28
or a Non-Expanded Off-Normal Test Report using
Sked Function Code 29. To generate this event, one
or more points must be in an off-normal state at the
time the Sked executes. Expanded Off-Normal Test
Reports include the Off Normal Test Report Event as
well as panel-wide summary of off-normal point and
system conditions. Non-Expanded Off-Normal Test
Report Events are sent only when a point is in the off-
normal state but sends only the Off-Normal Test
Report Event.
Sending Status Reports
Automatic: To send a Status Report automatically
that includes the events shown in the footnotes in
Table 9, enable Sked Function Code #10 in the
Skeds section of the program.
Manual: To send a Status Report manually that
includes the events shown in the footnotes in Table
9, enter [COMMAND][4][2] at the keypad. Refer to
the Send Report prompt on page 57.
Sending off-normal conditions as a Status Report
following a Test Report is required by some
automation systems. Sending off-normal conditions
as a Non-status Report that follows a Test Report is
required for other automation systems.
An off-normal condition is any point that is missing,
trouble, supervisory, or in alarm. Also, points not
cleared at the keypad report as off-normal.
Table 9: Test Reports
Report
Selection
s
Report
Description
R# S: Alarm
1
Yes, No Status Alarm
R# S: Trouble
1
Yes, No Status Trouble
R# S:
Supervised
2
Yes, No Status Supervised
R# Status
Report
Yes, No Status
R# S: Open
1
Yes, No Status Open
R# S: Close
1
Yes, No Status Close
R# Test Report Yes, No Test
R# S:
Perimeter Inst
1
Yes, No
Status Perimeter
Instant Arm
R# S:
Perimeter
Delay
1
Yes, No
Status Perimeter
Delay Arm
R# S: Fire
Supv
2
Yes, No
Status Fire
Supervision
R# S: Fire
Alarm
3
Yes, No
Status Fire Alarm
Report
R# S: Fire Trbl
2
Yes, No Status Fire Trouble
R# S: Msng
Fire
2
Yes, No Status Fire Missing
R# S:
MsngBurgTr
2
Yes, No
Status Burg
Missing Trouble
R# S:
MsngBurgAl
2
Yes, No
Status Burg
Missing Alarm
R# S:
FireSpMsng
2
Yes, No
Status Fire
Supervision
Missing
R# S:
SuperMsng
2
Yes, No
Status Non-fire
Supervision
Missing
R# S:
DrLeftOpen
4
Yes, No
Status Door Left
Open
1
Information about this condition is sent with a Status
Report.
2
Information about this condition is sent as S: Trouble
Event with a Status Report.
3
Information about this condition is sent as S: Alarm
Event with a Status Report.
4
This event is not transmitted for the D7212GV3. Use
only the default setting.