D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 32
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
D1260
1. Refer to Figure 2 on page 7 to access Keypad
Programming and navigate to the Area
Parameters option. Press [ENT].
2. The keypad reads Area Number 1 – 8.
3. Enter the area number you wish to configure and
press [Enter]. The current area status shows (for
example, Area 1 On: Yes).
4. Press the Edit softkey to change the area’s
status.
5. Press the Yes or No softkey, and then press the
Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection is configured.
6. When the keypad reads Area Status, press the
Account Number softkey. The keypad shows
the currently configured account number.
7. Press the Edit softkey to change the account
number.
8. Use the softkeys and the number buttons on the
keypad to enter the new account number. The
Backspace softkey allows you to erase
characters. The Clear softkey allows you to clear
the entire account number. When entering a
letter character, press the letter's softkey to
select it. The Previous and Next softkeys
advance through the letter characters (A, B, C, D,
E, F).
9. Press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection is configured.
A# Force Arm/Bypass Max
Default: 1
Selection:
0 to 99
Specify the maximum number of combined
Controlled points that can be faulted or bypassed
when arming this area.
Refer to the prompts P## Force Arm Returnable
and P## Bypass Returnable in Section 4.2 Point
Responses on page 81 for returning a point to the
system when the point returns to normal or when the
area is disarmed.
Users can bypass more points than the
number entered here during the
disarmed state. It is only when the user
attempts to Bypass Arm an area (or
areas) that this restriction is enforced.
A# Delay Restorals
Default: No
Selection:
Yes or No
Yes Point Restoral Report is not sent
until the bell time expires or user
acknowledges alarm condition.
No
Restoral Reports are sent when
point restores, regardless of bell
time.
A# Exit Tone
Default: Yes
Selection:
Yes or No
Sounds an exit tone during exit delay at all keypads
assigned to this area.
You can turn off exit tones for individual
keypads by programming the
appropriate CC# 1 to 8 as No in CC#
Exit Tone.
A# Exit Dly Time
Default: 60
Selection:
0 to 600 (in 5 sec increments)
Exit delay time for this area when Master Exit or
Perimeter Exit arming.
Points programmed for instant alarm
response generate alarms immediately,
even during exit delay. To avoid instant
alarms on points adjacent to the
perimeter when leaving the area,
program P## Type in the Point Index
as 3 (Interior Follower).
For SIA CP-01 Compliance
The Exit Delay Time must be between 45 sec and
255 sec.
A# Auto Watch
Default: No
Selection:
Yes or No
Yes When the area is disarmed, Watch
Mode turns on automatically.
No When the area is disarmed, Watch
Mode must be turned on or off
manually.