P## Point Response
Default: Refer to the program record sheet
Selection: 0 to F
Controlled (Non-24-Hour Points)
Point Response 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open I I I I D D I I D I I I I I T
Armed Short I I I I I I D D D I I I I I I
Disarmed Open T T T I I T I T
Disarmed Short T T T I T I I
24-Hour Points
Point Response 0 1 2 3 4 5 6 7 8 9 A B C D E F
Open I T I T I T S T S S
Short I I T T I T T S S S
Key: I = Instant alarm
D = Delayed alarm
T = Trouble
S = Supervisory
Blank = Audible or visual response
Example of Controlled point:
Point Type = 1
Point Response = 8
Perimeter point with delayed alarm response when
armed (opened or shorted) and no response when
disarmed.
Example of 24-hour point:
Point Type = 0
Point Response = 8
24-hour point with supervisory response when open
and a trouble response when shorted.