D8125 | Installation and Operation Guide | UL Applications
Bosch Security Systems B.V. | 2020.04 | F01U036298-15 3
UL Applications
The control panel enclosure and POPIT modules required for specific UL or NFPA ZONEX system applications are
listed below. The D8108A Attack-Resistant Enclosure meets or surpasses the requirements for all of these
applications. A D8109 Fire Enclosure can be used for fire applications. Any mercantile combination fire and burglar
system must use the D9127U/T POPIT Module. Refer to UL 681 “Installation and Classification of Mercantile and
Bank Burglar Alarm Systems” for further details on installation requirements.
US Residential
UL Household Fire/NFPA 72 D8103 U or T
UL Household Burglar D8103 U or T
Commercial
UL Local Burglar/Police Connected Burglar D8108A T*
UL Central Station Burglar D8103 T*
UL Central Station Burglar D8108A T*
UL Local Fire/NFPA 72 D8109 U or T
UL Central Station Fire/NFPA 72 D8109 U or T
UL Remote Station Fire/NFPA 72 D8109 U or T
UL Electrically Activated Transmitter D8109 U or T
CA
ULC-ORD C1023 - Household Burglar Alarm System Units D8103 U or T
ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems D8108A T*
Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems D8108A T*
CAN/ULC S304 - Signal Receiving Centre and Premise Alarm Control Units D8109 U or T
CAN/ULC S545 - Residential Fire Warning Alarm Systems Control units D8109 U or T
* A model “U” POPIT mounted within a tampered enclosure can be used in place of a model “T” POPIT.
The following describes the classification of the Bosch Security Systems modules. Please reference the NFPA 72 for
the specific details of IDC, SLC, NAC conditions.
D125B (Powered Loop Interface) B
D129 (Dual Class A Initiation Module) A
D192G (Bell Supervision Module) B
D8125 (Zone Expansion Module) B
D9127U/T (Point of Protection Module) B