D8125 | Installation and Operation Guide | 5.0 Troubleshooting
.
Bosch Security Systems B.V. | 2020.04 | F01U036298-15 35
5.1.2.1 Extra Points
If the control panel is not in the service walk test mode when an extra point trips, the control panel responds
to it as a local TROUBLE event at the control center or central station (see Section 2.1.3 Routing in the
D9412G/D7412G Program Entry Guide P/N: (47775). It displays the custom text for the point number set in
the point’s dipswitch or on-board point location.
When an extra point is tripped during the service walk test, it reports as an EXTRA point in the control panel’s
event log and at the local printer (if installed). Once an extra point is identified you can check the
programming to see if it has a Point Index programmed. You can then determine if the point index is
appropriate for the application and that the area assignment is correct.
5.2 D8112G1/G2
5.2.1 Introduction
This section is provided to aid in correcting problems with installed POPEX and POPIT Modules. To prevent
problems from occurring, read all of the pertinent documentation (Omegalarm D8112:MAIN and Omegalarm
D8112:AUX Program Entry Guides, Omegalarm D8112:PTEXT Program Entry Guide if a D1252A display is used,
and the previous sections of this guide), and verify that the product handler programs are at the following
revision levels (or higher): D8112:MAIN A7, D8112:AUX B1, D8112:PTEXT A5.
5.2.2 D1252A POPIT Activity
If the D1252A Keypad does not display POPIT activity:
1. Verify D8112:MAIN product handler program items 122 ExRAM and 123 16ChDisp are both
programmed [YES].
2. Verify D8112:AUX product handler program item 2.1 ZONEX is programmed [YES].
3. Verify that the revision level of the 8112:AUX product handler is B1 or higher. If you are not sure
what revision level of the D8112:AUX product handler was loaded into the control panel:
Verify that your D5100 programmer contains the D8112:AUX.B1 or higher product handler.
Disconnect terminals 30 and 31 from the D8112.
Copy the D8112:AUX file out of the D8112.
Re-Load the same 8112:AUX file into the D8112.
Be sure to perform a disable/restart on the D8112 (momentarily connect Terminal 32 to Terminal
29) before or after programming or copying.
4. Verify the assignments of POPIT Modules to master zones in the D8112 Handler program items 2.5
Z1Points through 2.12 Z8Points.
5. Verify that D8112:AUX Product Handler program item 6.1 MLogEN is [YES].
5.2.3 Missing POPIT Modules
If the D1252A Keypad displays a “missing POPIT” status code (Example: ZN101M6):
1. Check the programming of horizontal or vertical mode 2.2 Hrzntl [Yes/No] in the D8112 handler.
2. Verify that the appropriate vertical or horizontal switch setting chart was used (see Table 5 and
Table 6) and that the POPIT switch settings are correct (refer to Section 4.3.2 POPIT Module
Installation).
3. Verify the assignments of POPIT Modules to master zones in the D8112 handler program items 2.5
Z1Points through 2.12 Z8Points.
Note: If all 126 points of protection are used in the horizontal mode, 2.12 Z8Points must be programmed with a
[14]. In Horizontal mode, you are allowed fourteen points on Zone 8, seven on POPEX 1 and seven on
POPEX 2. In Vertical mode, you are allowed fifteen points on Zone 8 and fifteen on Zone 4.
4. Check the wiring of the POPEX Module to the D8112 control panel (refer to Figure 4 and Section 4.3
D8112G1/G2.

Other manuals for Bosch D8125

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch D8125 and is the answer not in the manual?

Bosch D8125 Specifications

General IconGeneral
Housing color-
Input voltage12 V
Connectivity technologyWired
Weight and Dimensions IconWeight and Dimensions
Depth80 mm
Width130 mm
Height20 mm

Related product manuals