DS7200V2-UK Installer's Guide Copyright 2007 Bosch Security Systems, Inc. P/N: 4998152533-02 Page 125
PART V: REFERENCE MATERIALS
Event #
Panel Log
SIA Report
SIA Report Data
Contact ID Report
Event Description
Zone Types
Linked to Event
RPS
Event
Group
Status
Reports
17 Cross,Unverified Unverified
Event Burglary
ri {area} BG {loop} 378 Cross-zone
Trouble
A fault on one non-
Cross Zone Option
selected. This is not
an alarm event.
any with Cross
Zone Option
3
18 Alarm Exit Error Exit Alarm ri {area} EA {loop} 374 Exit Error
(zone)
Zone faulted at the
end of Exit Delay.
11- Delay 1
12- Delay 2
3
19 Alrm Recent Clse Recent Closing
ri {area} CR {loop} 134 Entry/Exit
Alarm event within 2
minutes of closing.
11- Delay 1
12- Delay 2
3
20 Alrm Recent Clse Recent Closing
ri {area} CR {loop} 130 Burglary
Alarm event within 2
minutes of closing.
10- Keyswitch
13- Follower
14- Instant
3
21 Auto On Extended
Closing Extend
ri {area} CE {user} 464 Auto-
Extended
Auto On Sked
delayed one hour by
user. Report follows
Open/Close routing.
10
22 Battery Low System Battery
Trouble
YT 302 Low System
Battery
Panel battery is low. 12 R S
23 Battery Missing System Battery
Missing
YM 311 Battery
Missing/Dead
Panel battery is
missing. Very low,
shorted, or open
batteries are reported
as missing.
12 R S
24 Rstrl Batt Low System Battery
Restoral
YR 302 Low System
Battery
Battery restoral from
low battery.
12 R S
25 Rstrl Bat Missng System Battery
Restoral
YR 311 Battery
Missing/Dead
Battery Restoral from
missing battery
12 R S
26 Bypass,Fire,User Fire Bypass ri {area} FB {loop} 571 Fire bypass Selective bypass by
user, fire zone types
1- Fire
2- Fire with
Alarm
Verification
15
27 Bypass,Fire,
RPS
Fire Bypass ri {area} FB {loop} 571 Fire bypass Selective bypass by
RPS, fire zone types.
1- Fire
2- Fire with
Alarm
Verification
28 Bypass,Ctrl,User Burglary
Bypass
ri {area} BB {loop} 570 Zone/Sensor
bypass
Selective bypass by
user, zone types.
10 to 15- Zone
Types
15
29 Bypass,Ctrl,
RPS
Burglary
Bypass
ri {area} BB {loop} 570 Zone/Sensor
bypass
Selective bypass by
RPS, zone types.
10 to 15- Zone
Types
30 Bypass,24hr,User Burglary
Bypass
ri {area} BB {loop} 572 24-Hr Zone
Bypass
Selective bypass by
user, 24-hour non-fire
zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
15
31 Bypass,24hr,
RPS
Burglary
Bypass
ri {area} BB {loop} 572 24-Hr Zone
Bypass
Selective bypass by
RPS, 24-hour non-
zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
32 Bypass,Forced Zn Burglary
Bypass
ri {area} BB {loop} 570 Zone/Sensor
bypass
Zone force armed at
force arming.
10 to 15- Zone
Types
15
33 Bypass,Swinger Burglary
Bypass
ri {area} BB {loop} 575 Swinger Shunt
Zone Swinger
Shunted.
All zone types 15
34 UnBypss,Fire, Usr Fire Bypass ri {area} FU {loop} 571 Fire bypass User cleared bypass
types.
1- Fire
2- Fire with
Alarm
Verification
15
35 UnBypss,Ctrl,Usr Burglary
Unbypass
ri {area} BU {loop} 570 Zone/Sensor
bypass
User cleared bypass
(unbypass), zone
types.
10 to 15- Zone
Types
15
36 UnBypss,24hr,Usr Burglary
Unbypass
ri {area} BU {loop} 572 24-Hr Zone
Bypass
User cleared bypass
(unbypass), 24-hour
zone types.
3 to 9- 24-hour,
Non-Fire Zone
Types
15
Table 47: Control Panel Events and Reporting Formats (continued)