EasyManua.ls Logo

Bosch rexroth A4VSO 10 Series - Installation Instructions

Bosch rexroth A4VSO 10 Series
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RE 92050-01-X-B2/2019-08-23, BoschRexrothAG
43 Axial piston variable pump | A4VSO Series 10, 11 and 30
Installation instructions
Installation instructions
General
The axial piston unit must befilled with hydraulic fluid and
air bled during commissioning and operation. This must
also beobserved following alonger standstill astheaxial
piston unit may empty viathehydraulic lines.
Particularly inthe installation position "drive shaft
upwards", filling and air bleeding must becarried out
completely asthere is,for example, adanger ofdry
running.
The leakage in the housing area must be directed to the
reservoir via the highest drain port (T, K
1
, K
2
, R(T)).
For combination pumps, the leakage must bedrained off
ateach single pump.
Ifashared drain line isused for several units, make sure
that therespective case pressure ineach unit isnot
exceeded. The shared drain line must bedimensioned
toensure that themaximum permissible case pressure
ofall connected units isnot exceeded inany operating
conditions, particularly atcold start. Ifthis isnot possible,
separate drain line must belaid, ifnecessary.
To achieve favorable noise values, decouple all connecting
lines using elastic elements and avoid above-reservoir
installation.
In all operating conditions, the suction and drain lines must
flow into the reservoir below the minimum fluid level.
Thepermissible suction heighth
S
results from the total
pressure loss. However, it must not behigher than
h
Smax
=
800mm. The minimum suction pressure
atportSmust also not fall below 0.8bar abs. during
operation and during acold start.
Make sure toprovide adequate distance between suction
line and drain line forthe reservoir design. This prevents
the heated, and possible foaming return flow from being
drawn directly back into the suction line.
Notice
Incertain installation positions, an influence
ontheadjustment orcontrol can beexpected. Gravity,
dead weight and case pressure can cause minor
characteristic shifts and changes inactuating time.
Installation position
See thefollowing examples 1 to7.
Further installation positions are available upon request.
Recommended installation position: 1 and 2
Below-reservoir installation (standard)
Below-reservoir installation means that theaxial piston unit
isinstalled outside ofthereservoir below theminimum
fluid level.
Installation position Air bleed Filling
1
SB
h
t min
h
min
R(L)
T
S
F
R(L) + F S + R(L)
2
SB
h
t min
h
min
R(L)
T
S
F
T + F S + T
3
SB
h
t min
h
min
R(L)
T
U
S
F
T + F S + T + U
For key, see page44.

Table of Contents

Related product manuals