6 720 800 095 (2014/05)Therm 6000S
Installation instructions | 27
Press and hold "Program" button and press ON/OFF button
to turn appliance ON (Fig. 42).
Fig. 42 Gas tunning mode
As soon as '188' is displayed, release "Program" button
, and the display reads P2.
Press or until P1 appears.
For inlet gas pressure adjustment see values in Table 8 :
Turn on high volume of hot water ow (at least 15 l/m) and
burner will light. If heater display reverts to P2, open more
hot water xtures to allow sucient ow. Press until
P1 reappears on the display.
Operate all other gas appliances on same gas piping system
at maximum output.
Record lowest operating gas pressure reading in Table 7 .
Gas pressures lower than 2,0 kPa for Natural Gas or 3,0 kPa
for Butane will result in insu
icient degree rise to the hot
water being used, reduced hot water volume, possible error
code faults and must be corrected.
Check gas pipes dimensions.
8.3 Adjusting CO
2
(carbon dioxide)
When the gas pressure is correct:
Press ON/OFF button to turn o the appliance.
Remove plastic screw on the exhaust collar as seen in
Fig. 43.
Fig. 43 Measuring port
Insert CO
2
analyser probe into the measuring port. The tip of
the probe should be in the center of the ue pipe (approx
40mm inserted). Avoid air gaps between probe and
measuring port as they can alter readings.
While holding the Program (P) button, press the ON/OFF
button to turn ON the heater (see Fig. 44).
Fig. 44
While holding the Program button, press the ON/OFF
button to tur
n ON the heater. As soon as ‘188’ ashes on the
display, release the Program button. The display should now
read P2.
Press or button until “P1” appears on display.
NOTE: While in this mode the appliance will
run constantly at maximum power and allow
maximum water ow.
Gas type GN Butane
kPa 2,0 3,0
Table 8
The CO2 can only be adjusted by a certied
gas technician with a calibrated CO
2
analyser.
CAUTION:
One factor that may aect CO
2
levels is
improper gas pressure.
Check and adjust gas pressure, see
chapter 8.2.
6720608 920-18.1AL