6 720 800 095 (2014/05) Therm 6000S
30 | Installation instructions
8.4 Program values
This section describes details on programming the appliance.
For most applications the factory default values will provide
robust and stable operation.
CAUTION: Misadjusted program values
can lead to appliance malfunction, errors,
and service calls.
Program Description Factory default Min Max Comment
P1 Maximum Power N. Gas: 40
LPG: 37
21 N. Gas: 40
LPG: 37
See chapter 8.2.
Note: reducing P1 values below maximum
will reduce maximum power of the
appliance.
P2 Minimum Power N. Gas: 8
LPG: 7
N. Gas: 8
LPG: 7
20 See chapter 8.2.
P3 Remote
Controls installed
_0 _0 6 See chapter 4.6.
P4 Access to
Diagnostic Mode
E 0d 10f See chapter 8.5.
P5 Cascade Mode nO nO CC To activate the cascade mode it's necessary
to install the “kit cascade” (cod. 7 736 500
272)
P6 Temperature Unit °C °F °C See chapter 8.5.
P7 Appliance Type nO Cd
(condensing)
nO Condensing / Non-condensing
note: incorrect setting will cause errors.
P8 Back light dE dE On dE: turns back light o after 60 seconds
from last button pushed.
ON: turns backlight on permanently.
P9 Fan Purge Runs secondary fan and primary fan when
P9 is selected by depressing the “P” - button
PH Cascading type IC IC SC
This menu is only available when cascade
mode is selected CC.
PC Master/Slave
mode
CS CS Cn
Table 12