EasyManua.ls Logo

Brooks MFM - 2.8 Electrical Interfacing (Non-Profibus)

Brooks MFM
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Manual
X-TMF-MfS-MFC-eng
PN 541-C-061-AAG
November, 2008
MF Smart Series
12
2.7 In-Line Filter
An in-line lter is installed, as standard, in the instrument’s inlet to prevent any
foreign material entering the ow sensor or control valve. The ltering element
should be periodically replaced or ultrasonically cleaned. Apply only clean
gasses on Mass Flow Meter / Controllers.
2.8 Electrical Interfacing (not for Probus)
The installation of Smart TMF involves connecting to terminal strips. For
details of correct installation, see gure 2-2 and Table 2-2, 2-3 and 2-4.
Table 2-1: Pin conguration
Figure 2-2: Electrical compartment
Table 2-2: Electrical connection 9-pins terminal
PIN NO: FUNCTION
1 VSUP +
2 SUPCOM
3 NC
4 SIGCOM
5 VSIG
6 ISIG
1 TxD / A+
2 RxD / A-
3 TTLALM
4 VREF
5 VOR
6 NC
7 CMDCOM
8 VCMD
9 ICMD
pin *Function Controller Meter
1TxD/A+RS-232/RS-485 TxD/A+ ••
2RxD/A-RS-232/RS-485 RxD/A- ••
3 TTLALM(TTL) Open collector alarm output ••
4VREF+5 Vdc ref. output•
5VOR Valve override input•n.a.
detcennoc toNCN6
7CMDCOMSetpoint return (-)•n.a.
8VCMD0 (1)-5 Vdc Setpoint input (+)• n.a.
9ICMD0 (4)-20 mA Setpoint input (+) •n.a.
* Abbreviation for the function description can be found under the top cover
Section 2: Installation

Table of Contents

Related product manuals