EasyManua.ls Logo

Brooks MFM - Figure 2-3: Open Collector

Brooks MFM
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Manual
X-TMF-MfS-MFC-eng
PN 541-C-061-AAG
November, 2008
MF Smart Series
13
Section 2: Installation
Digital communication (pins 1 and 2)
(pins 1 and 2) are available for connecting the device to the TxD/A+ or
RxD/A-lines for RS-232/RS-485 communications.
NOTE: Either RS-232 or RS-485 should be specied at the time of ordering.
See section 2.7 for details of how to congure the p.c. board.
Alarm (pin 3)
A (TTL) Open Collector alarm output is available.
Type of used transistor is NPN.
Figure 2-3: Open Collector
5 Vdc reference (pin 4)
A +5 Vdc ref. voltage is available on (pin 4). This can be used to set the Set point
with the aid of an externally locate potentiometer (10 turn 2 KOhm suggested).
Valve override (pin 5 Controller models only)
To open or close the control valve independently of the Set point signal
(e.g. for safety reasons), (pin 5) is available to carry a valve override signal.
Leave oating (i.e. not connected) to allow for normal control operation.
5 Vdc Valve Open
≤ 0 Vdc Valve losed
NOTE: The valve override command on pin 5 takes precedence over the
communication-mediated valve override command.
Analogue Setpoint Input (pins 7, 8 or 9; Controller models only)
The MF-series Smart Mass Flow Controller can be used either with a current
or voltage Set point. To use the current Set point, connect the Set point signal
to (pin 9) and the Set point return signal to (pin 7) on the terminal (jumper J1
must be in place refer to Figure 2-6). To use the voltage Set point, connect the
Set point signal to (pin 8) and the Set point return to (pin 7).
Power Supply (pins 1 and 2)
The power supply is connected via (pin 1) (+15 to +28 Vdc) and (pin 2)
(power supply common).

Table of Contents

Related product manuals