Principles of operation
Logamatic EMS RC35 programming unit - Subject to technical modifications
16
4
4. The SERVICE\SETTINGS menu opens.
Turn rotary selector anti-clockwise until boiler data is
selected.
5. Press to select boiler data.
Menu SETTINGS\BOILER opens.
6. To change the value, hold down
(the value starts flashing) and turn rotary selector at the
same time.
7. Release .
The value stops flashing. The modified value is saved.
8. If you have carried out this example as practice only, make
sure that the original setting is retained.
To do so, repeat steps 6 and 7 if necessary.
9. Press to go back one step.
-or-
To finish entering the settings: press several times or
shut the flap.
The standard display re-appears.
You can enter all settings in the SERVICE MENU using this procedure.
Operation Result
Tab. 4 How to use the service menu (example)
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1
SETTINGS\BOILER
What type of building
do you have?
medium
SETTINGS\BOILER
What type of building
do you have?
medium
SETTINGS\BOILER
What type of building
do you have?
light
SETTINGS\BOILER
What type of building
do you have?
medium