System settings (Service menu â Settings)
6
Example:
Fig. 6 This greatly simplified example shows how the adjusted outside temperature follows the
outside temperature, but does not reach its extreme values.
1 Current outside temperature
2 Adjusted outside temperature
6.1.2 Minimum outside temperature
The minimum outside temperature is the mean of all the coldest outside temperatures of recent
years, and helps to determine the heating curve. The value can be taken from the heat requirement
calculation which should be done for every building, or from the climatic zone chart for your region.
With the factory settings, changes in the outside temperature affect the calculation of
weather-compensated control after no more than three hours (30 x 6 minutes =
180 minutes).
B To monitor the calculated, adjusted outside temperature and the currently captured
outside temperature: open the menu diagnosis\monitor valueîboiler / burner.