System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
28
6
Heating curve
std. tmp. ( – 10 °C) 30 °C to 90 °C 75 °C
(radiator,
convector)
45 °C
(floor)
The value in brackets is the setting
for the minimum outside temperature
(Æ page 27). Adjustment only if the
control type is set to “outside temp.
contr.” ( Æ page 32).
max flow temp. radiator,
convector:
30 °C to 90 °C
1)
floor:
30 °C to 60 °C
radiator,
convector:
75 °C
floor: 50 °C
Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 32).
Enter the maximum
flow temperature:
Adjustment only if the control type is
set to “room temp. contr.”
( Æ page 32).
min flow temp. 5 °C to 70 °C 5 °C Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 32).
Enter the minimum flow
temperature:
Adjustment only if the control type is
set to “room temp. contr.”
( Æ page 32).
rm. tmp. offset – 5.0 K to +5.0 K 0.0 K Offset of heating curve.
Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 32).
Enter the maximum room
influence:
0 K to 10 K 3 K Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 31)
Which type of reduction
should be implemented?
Outdoor setback
mode,
reduced operation,
Room setback
mode (only if
RC35 or RC2x has
been assigned to
the heating circuit),
shut-down mode
Outdoor
setback
mode
Night setback (Æ page 33)
Menu item Input range
Factory
setting Other information
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1