System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
30
6
What is the desired
maximum flow
temperature?
25 °C to 60 °C 45 °C
2)
For how many days
should maximum flow
temp. be maintained?
0 days to 20 days 4 days
2)
Every how many days
should the flow temp.
be reduced?
direct normal
operat., every day,
every 2nd day to
every 5th day
Every day
2)
By how many K should
the flow temp. be
reduced each time?
0 K to 20 K 5 K Adjustment only if, for flow
temperature reduction,“direct normal
operat.” has not been selected.
4)
Do you wish to change
the switching
programme?
yes, no no When selecting “yes” the system
jumps to the heating circuit
switching program.
Should the switching
programme be optimised?
yes, no no Start and stop times are
automatically adjusted according to
the outside temperature, room
temperature and building type (heat
storage capacity).
What reduction mode
should be used for
holiday?
Outdoor setback
mode,
reduced operation,
Room setback
mode, shut-down
mode
Outdoor
setback
mode
See page 33.
Adjustment “Room setback mode”
only if a remote control (e.g. RC2x)
has been allocated to the heating
circuit.
If “reduced operation” has been
selected, the standard night temper-
ature will be applied.
What outside temp.
should be used?
– 20 °C to
+10 °C
5 °C Temperature threshold for outdoor
setback mode (Æ page 33).
Adjustment only if setback mode for
holiday was set to “Outdoor setback
mode.”
1) The setting range can be limited, subject to boiler.
2) Not possible or available on boilers with UBA1.x or DBA.
Menu item Input range
Factory
setting Other information
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1