Logamatic EMS RC35 programming unit - Subject to technical modifications
35
System settings (Service menu – Settings)
6
In parameter At what outside temp. should reduction be interrupted?, you can set an outside
temperature threshold (relative to the adjusted outside temperature, Æ page 24).
Fig. 8 shows how the frost protection function works, with and without this parameter activated.
Settings selected: frost protection by outside temp.; frost protection temp.C.
Fig. 8 Effects of the parameter “At what outside temp. should reduction be interrupted?”.
Left: parameter set “OFF” (factory setting). Right: parameter set to – 15 °C.
T
A
Outside temperature
T
V
Flow temperature
1 Standby
2 Reduced mode (at set nighttime room temperature)
3 Heating mode (at set daytime room temperature)
The heating system changes from reduced mode to standard heating mode [3] if the outside
temperature falls below – 15 °C. This allows smaller heating surfaces to be utilised.
T
A
T
A
T
V
5°C
T
V
5°C -15°C
2
3
1
2
1
6 720 618 477-07.1RS

Other manuals for Buderus Logamatic EMS RC35

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logamatic EMS RC35 and is the answer not in the manual?

Buderus Logamatic EMS RC35 Specifications

General IconGeneral
BrandBuderus
ModelLogamatic EMS RC35
CategoryController
LanguageEnglish

Related product manuals