4 Regulations and operating conditions
6 720 646 864 (12/2010) – Technical guide Logano GE315, GE515 and GE615
21
4 Regulations and operating conditions
4.1 Extracts from the regulations
The Ecostream cast iron boilers Logano GE315, GE515
and GE615 comply with the requirements of EN 303 and
are approved up to ≤ 120 °C according to the Pressure
Equipment Directive. They are approved for a permissible
operating pressure of up to 6 bar and for heating systems
compliant with the requirements of DIN-EN 12828 and
the additional requirements of EN 12953-6.
Observe the following regarding creation and operation of
the system:
• Technical building rules
• Legal regulations
• Local regulations
Installation, oil and gas connection, flue gas connection,
commissioning, power supply, maintenance and repair
work must only be carried out by authorised contractors.
Permits
The installation of an Ecostream cast iron boiler with gas
burner may need to be notified to and approved by the
relevant gas supply utility.
We recommend clarifying the match between boiler and
flue system with the relevant bodies at the planning stage.
Where required, inform your local flue gas inspector prior
to commissioning. It may be necessary to obtain a permit
for the flue system at regional level.
Annual inspection and demand-dependent
maintenance
To ensure functional reliability and energy quality, an
inspection by a heating contractor is recommended at
least annually. If any condition requiring maintenance
work is identified in the course of an inspection, it should
be carried out as required.
We recommend system operators conclude a
maintenance and inspection contract with the heating
contractor or burner manufacturer.