4 Regulations and operating conditions
6 720 646 864 (12/2010) – Technical guide Logano GE315, GE515 and GE615
30
4.8.12 Correction factor
The correction factor can be found at the intersection of
the horizontal row containing the Ca(HCO
3
)
2
figure for
calculation with V
max
, and the vertical column containing
the Ca(HCO
3
)
2
figure for the fill or top-up water.
Water volume added × correction factor = corrected
water volume.
Total water volume + corrected water volume = new total
water volume.
Ca(HCO
3
)
2
figure to
calculate V
max
Ca(HCO
3
)
2
figure for the fill or top-up water
mol/m
3
0.3 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
0.3
1.0 1.7 3.3 5.0 6.7 8.3 10.0 11.7 13.3 15.0 16.7
0.5 0.6
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
1.0 0.3 0.5
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
1.5 0.2 0.3 0.7
1.0 1.3 1.7 2.0 2.3 2.7 3.0 3.3
2.0 0.1 0.3 0.5 0.7
1.0 1.3 1.5 1.7 2.0 2.3 2.5
2.5 0.1 0.2 0.4 0.6 0.8
1.0 1.2 1.4 1.6 1.8 2.0
3.0 0.1 0.2 0.3 0.5 0.7 0.8
1.0 1.2 1.3 1.5 1.7
3.6 0.1 0.1 0.3 0.4 0.6 0.7 0.9
1.0 1.1 1.3 1.4
4.0 0.1 0.1 0.2 0.4 0.5 0.6 0.8 0.9
1.0 1.1 1.3
4.5 0.1 0.1 0.2 0.3 0.4 0.5 0.6 0.8 0.9
1.0 1.1
5.0 0.1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
1.0
Tab. 14 Correction factor