9 Flue systems
6 720 646 864 (12/2010) – Technical guide Logano GE315, GE515 and GE615
76
9.2.2 Ecostream cast iron boilers Logano GE515 and Logano GE615
Output
Rated
heat
input
Flue
outlet
Req.
draught
Max. flue
gas
temperature
Min. flue gas
temperature
1)
Oil as fuel Gas as fuel
Logano
Boiler
size
CO
2
content
Flue gas
mass flow
rate
CO
2
content
Flue gas
mass flow
rate
Stage [kW] [kW] DN [Pa] [°C] [°C] [%] [kg/s] [%] [kg/s]
GE515
240
2
2)
240
201
259.7
215.6
250 0
183
164
171
152
13.0
0.1102
0.0915
10.0
0.1106
0.0919
1
3)
144 152.4 138 126 0.0647 0.0649
295
2
2)
295
241
319.0
257.8
183
161
171
149
0.1354
0.1094
0.1359
0.1098
1
3)
177 187.3 138 126 0.0795 0.0798
350
2
2)
350
296
377.1
316.6
177
161
165
149
0.1601
0.1344
0.1606
0.1349
1
3)
210 222.2 140 128 0.0943 0.0947
400
2
2)
400
351
429.6
374.6
171
157
159
145
0.1824
0.1590
0.1830
0.1596
1
3)
240 254.0 129 117 0.1078 0.1082
455
2
2)
455
401
489.2
428.4
172
159
160
147
0.2077
0.1818
0.2084
0.1825
1
3)
273 288.9 130 118 0.1226 0.1231
510
2
2)
510
455
547.8
488.2
174
164
162
152
0.2325
0.2072
0.2334
0.2080
1
3)
306 323.8 140 128 0.1374 0.1379
GE615
570
2
2)
570
511
616.2
546.5
360 0
185
170
173
158
13.0
0.2615
0.2320
10.0
0.2625
0.2328
1
3)
342 362.0 140 128 0.1537 0.1542
660
2
2)
660
571
713.5
610.7
180
170
168
158
0.3028
0.2592
0.3039
0.2602
1
3)
396 419.0 140 128 0.1778 0.1785
740
2
2)
740
661
800.0
707.0
135
170
168
158
0.3396
0.3001
0.3408
0.3012
1
3)
444 470.0 140 128 0.1995 0.2002
820
2
2)
820
741
886.5
792.5
180
170
168
158
0.3763
0.3364
0.3776
0.3376
1
3)
492 520.0 140 128 0.2207 0.2215
920
2
2)
920
821
994.6
878.1
185
170
168
158
0.4222
0.3727
0.4237
0.3741
1
3)
552 584.0 140 128 0.2479 0.2488
1020
2
2)
1020
921
1102.0
985.0
180
170
168
158
0.4678
0.4181
0.4694
0.4196
1
3)
612 648.0 140 128 0.2750 0.2760
1110
2
2)
1110
1021
1200.0
1092.0
180
170
168
158
0.5093
0.4635
0.5112
0.4652
1
3)
666 705.0 140 128 0.2992 0.3003
1200
2
2)
1200
1111
1297.0
1188.0
180
170
168
158
0.5505
0.5043
0.5525
0.5061
1
3)
720 762.0 140 128 0.3234 0.3246
Tab. 43 Flue gas parameters for the Ecostream cast iron boilers Logano GE515 and GE615
1) Basis for calculating the flue system to DIN-EN 13384-1
2) Parameters for the highest and lowest figures in the rated output range
3) Parameters for partial load with approx. 60 % of rated output