53
Par. Description Min. Max Default
C4 Compensation Coefficient.NTC only -2.0 2.0 0.5
and with Mode 1 or 2 & C19 = 2, 3 or 4.
Consider D=NTC2 - SET2 :
if C19 = 2
when D<=0 SET1=SET1
when D > 0 SET1=SET1+D*C4
if C19 = 3
when D>=0 SET1=SET1
when D < 0 SET1=SET1+D*C4
if C19 = 4
when NTC2 > SET2+P2, SET1=SET1+(D-P2)*C4
when NTC2 < SET2- P2, SET1=SET1+(D+P2)*C4
C5 Control action: 0=Prop(P), 1=Prop+Integ(P+I) 0 1 0
Parameters of the outputs
C6 Delay between on routines of 2 different outs 0 999’ 5’
C7 Minimum time between on routines
of the same output 0 5’ 0
C8 Minimum off time of the same output 0 5’ 0
C9 Minimum on time of the same output 0 15’ 0
C10 Status of the outputs with probe alarm: 0 3 0
0 = All relay de-energized
1 = All relays energized
2 = Direct action relays energised, all others de-energised
3 = Reverse action relays energised, all others de-energ.
Advanced set-up: list of parameters
+05-3015 • rel.3.0 interno ok 18-09-2002 14:31 Pagina 53