Technical features
57
General specifications
64
56
64
Additional errors
DIGITAL FILTER:
Operating range: 0 to 99.9% of the input scale
Filtering coefficient: 1 to 255
Filter action: alarms, serial and analogue outputs (fundamental
variables: V, A, W and their derived ones).
EVENT LOGGING: only with the module RS232+RTC mod-
ule. The max./min. values of the selected variables and the
alarm status are stored with reference to date (dd:mm:yy) and
time (hh:mm:ss). Max. capacity: 480 events.
VARIABLE PAGES: 4 variables per page; up to 27 pages, one
of which is completely programmable.
Harmonic Distortion Analysis
ANALYSIS PRINCIPLE: FFT
HARMONIC MEASUREMENT:
Current: up to the 50
th
harmonic
Voltage: up to the 50
th
harmonic
TYPE OF HARMONICS:
THD (VL1); THD odd (VL1); THD even (VL1); the same for
the other phases: L2 and L3.
THD (AL1); THD odd (AL1); THD even (AL1); the same for
the other phases: L2 and L3.
HARMONIC PHASE ANGLE:
The instrument measures the angle between the single
harmonics of V and the single harmonics of A expressed
as °, making it possible to understand if the harmonics are
generated or imported.
On three-wire systems, the angle cannot be
measured.