Installing the controller
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
6
If the controller’s address is 25, point the arrow on the
(
) switch to 2 and the arrow on
the
(
) switch to 5.
10's
1's
1
3
4
5
2
7
8
9
6
0
1
3
4
5
2
7
8
9
6
0
The factory default setting is
and must be changed to successfully install your controller.
Wiring for communications
The controller communicates using BACnet on the following types of network segments:
• MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
• ARC156 communicating at 156 kbps
For more networking details, see the Open Controller Network Wiring Installation Guide.
Wiring specifications for BACnet MS/TP and ARC156
Cable: 22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length: 2000 feet (610 meters)
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
To wire the controller to the BACnet network
1 Pull the screw terminal connector from the controller's power terminals labeled
and
(
).
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the controller’s screw terminals labeled
,
, and
.
Use the same polarity throughout the network segment.