Appendix D: Touchscreen settings
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
55
30MP Multi-chiller Chiller Linkage Source Address
Navigation:
Equipment Touch
Startup Wizard
>
Chiller Linkage Source Address
Point Name/Description
Range
Set up each Chiller #x Linkage Source Address using the following properties.
Navigate to the
Linkage
screen by clicking on the bottom.
Collector Network Number
The chiller's MS/TP network number. D:
R:
0
0 to 65,534
MSTP Address
: Set the MAC address of the chiller UPC Open controller. D:
R:
0
0 to 99