Installing the controller
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
15
4 Apply power and verify sensor readings.
Wiring an Equipment Touch to the controller
A single Equipment Touch is the only device you can wire to the controller's Rnet port. You can use a 2-conductor
cable instead of the standard 4-conductor Rnet cable and follow the instructions below.
NOTE
The Rnet communicates at a rate of 115 kbps.
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
1 Turn off the controller's power.
2 Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
3 Strip about .25 inch (.6 cm) of the inner insulation from each wire.
4 Wire the controller's
Rnet+
and
Rnet-
terminals to the terminals of the same name on the Equipment Touch's
connector.
NOTE
If using shielded wire, connect the shield wire and the ground wire to the
Gnd
terminal.
5 Turn on the controller's power.
6 Turn on the Equipment Touch.