Carrier 30MP - Unit Configuration Settings; Cooling Operation Settings; Power Failure Recovery

Carrier 30MP
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
33
Point Name/Description
Range
Shutdown
– When
Active
, provides a means to stop the chiller plant in an orderly
manner. All alarms are reset and only currently active alarms are displayed.
D:
R:
Inactive
Inactive/Active
Unit Configuration
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Configuration
>
Unit Configuration
Point Name/Description
Range
Cool Enable
– Enables or disables cooling operation. D:
R:
Enable
Disable/Enable
Cooling Lockout Temperature
– Cooling is inhibited below this outdoor air temperature. D:
R:
45°F
-65 to 80°F
Cooling Setpoint OA Reset
– Enables OA reset of the cooling water supply temp's
setpoint.
D:
R:
Disable
Disable/Enable
OAT CHW Supply Reset Low Limit
– The lowest outdoor air temperature which resets the
cooling water supply temp.
D:
R:
70°F
__°F
OAT CHW Supply Reset High Limit
– The highest outdoor air temperature which resets
the cooling water supply temp. Must be set above the configured
OAT CHW Supply Reset
Low Limit
.
D:
R:
90°F
__°F
Maximum OA CHW Reset
– The highest cooling water supply temp setpoint reset
allowed by the OAT.
D:
R:
10°F
0 to 25°F
RH Cooling Setpoint Reset
– Enables or disables reset of the cooling water supply
temp's setpoint, based on relative humidity.
D:
R:
Disable
Disable/Enable
Occupancy Schedules
– Enables or disables the occupancy schedule function. D:
R:
Disable
Disable/Enable
Power Failure Recovery
Power Fail Restart Delay
– On initial power up or after recovery from a power failure, the
controller delays starting any equipment for the configured value of this delay in seconds.
(Max delay time is 600 sec.)
D:
R:
120 seconds
0 to 600 seconds
Immediate Restart Time
– For a power failure less than this value (in minutes), the
control restarts all previous running chiller stages at 30 second intervals. (Max restart
delay time is 720 min.)
D:
R:
20 minutes
0 to 720 minutes