Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
35
Point Name/Description
Range
Defined Time for Rotation
– Specify the time of day (24 hour format) for automatic
rotation based on the method and schedule you selected.
(Not applicable to Runtime Equalization.)
D:
R:
8:00
1:00 to 24:00
Runtime Since Last Rotation
Chiller
Runtime
CH-1 0.0 hr
CH-2 0.0 hr
R: _hrs
Chiller Order
Chiller
Position
CH-1 1
CH-2 0
R 1 to 8
0 = not available
Setpoints
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Configuration
>
Setpoints
Point Name/Description
Range
Chilled Water Setpoint
- The chilled water temperature setpoint maintained by the chiller
plant. The setpoint is internally clamped so it will not exceed the highest freeze point
configured in any chiller.
D:
R:
44°F
40 to 80°F for water
-20 to 45°F for brine
Condenser Water Temperature
CW Min Load Setpoint
– The condenser water temperature setpoint at minimum load. D:
R:
65°F
50 to 85°F
CW Part Load Setpoint
– The condenser water temperature setpoint at partial load. D:
R:
70°F
50 to 85°F
CW Full Load Setpoint
– The condenser water temperature setpoint at full load. D:
R:
76°F
50 to 85°F