Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
37
High Entering Load Water Temp Alarm Limit
– The
must
exceed this value to generate an
Entering Load Water Temperature Alarm
. There is a fixed
hysteresis of 2
°F for return to normal.
D:
R:
125°F
90 to 150°F
Outdoor Air Temperature Alarm
– The
must drop below this value to
generate an
. There is a fixed hysteresis of 1 °F (.5 °C) for
return to normal.
D:
R:
-65°F
-65 to 40°F
– The
must exceed this value to generate
an
. There is a fixed hysteresis of 1 °F (.5 °C) for return to
normal.
D:
R:
245°F
100 to 245°F
Occupied High RH Alarm Limit
– The relative humidity sensor must exceed this value to
generate a
alarm in the occupied mode if
RH Cooling Setpoint
Reset (Unit Configuration)
is set to
. There is a fixed hysteresis of 5%rh for return to
normal.
D:
R:
100%rh
45 to 100%rh
– Determines the amount of delay before an occupied RH alarm is
generated when the controller transitions to the occupied mode. The delay time equals this
value multiplied by the difference between the sensor RH value and the occupied RH
setpoint plus 15 minutes.
D:
R:
5 minutes
0 to 30 minutes
Unocc High RH Alarm Limit
– The value that the relative humidity sensor must exceed to
generate a
in the unoccupied mode if
is set to
.
There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
100%rh
45 to 100%rh
>
>
>
– Defines whether the control monitors and uses
or
to control this equipment.
D:
R:
Leaving Water Temp
Leaving Water Temp
Entering Water Temp
Minimum # of Chillers to Run
– The least number of chillers you can run at the same
time.
D:
R:
1
1 to 8