Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
38
– (Additional Capacity Required) Determines the time delay before an
additional compressor stage can be added.
D:
R:
5:00 minutes
2:00 - 20:00 minutes
– (Reduced Capacity Required) Determines the time delay before an
additional compressor stage can be removed.
D:
R:
3:00 minutes
1:00 to 5:00 minutes
– This BACnet Object calculates the amount of capacity required to satisfy the
and allows access to the control loop's tuning parameters.
The following default values should be changed only by a technician trained in PID
Loop algorithms.
Action
Update Interval
Proportional
Integral
Derivative
Deadband
Bias
direct
0:30 (mm:ss)
100
0
0
0
0
Defines the type of fan output control. D:
R:
0-10 V
0-10 V
2-10 V
– This BACnet Object calculates the fan speed required to achieve the
desired condenser water temperature setpoint.
The following default values should be changed only by a technician trained in PID
Loop algorithms.
Action
Update Interval
Proportional
Integral
Derivative
Deadband
Bias
direct
1:00 (mm:ss)
10
2
0
0
0
Occ Contact Normal Logic State
–
Specifies the occupancy contact's normal logic state. D:
R:
Open
Open/Closed
RH Sensor Min Input Volts
– The lowest voltage that should be read from the hardwired
relative humidity (RH) sensor.
D:
R:
0.00 V
0 to 2.00 V
RH Sensor Max Input Volts
– The highest voltage that should be read from the hardwired
RH sensor.
D:
R:
5.00 V
0 to 5.00 V
RH Sensor Value @ Min Volts
– The % relative humidity that correlates to the hardwired
RH sensor's low voltage reading.
D:
R:
0%
0 to 40%
RH Sensor Value @ Max Volts
– The % relative humidity that correlates to the hardwired
RH sensor's high voltage reading.
D:
R:
100%
60 to 100%
– Allows using another controller's relative humidity value over the
network. The remote controller must be equipped with a network-accessible relative
humidity sensor value.
D:
R:
-999
2 to 100%