Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
39
– The system cool demand level being received over the
network.
D:
R:
0.00
0 to 3
System Outdoor Air Temperature
– Allows the controller to use an outdoor air
temperature value from the network. The remote controller must have a network-
accessible outdoor air temperature sensor value.
D:
R:
-999.00°F
-50 to 150°F
System Leaving Load Water Temperature
– Allows using another controller's leaving
load water temperature sensor value (system water temperature), to be read over the
network. The remote controller must have a network-accessible leaving load water
temperature sensor value .
D:
R:
-999.00°F
0 to 250°F
– Allows using another controller's Control Setpoint value to be
read over the network. The remote controller must have a network-accessible point.
D:
R:
-999.00°F
0 to 250°F
– Allows reading and using another controller's occupancy status
value over the network. The remote controller must have a network-accessible
Occupancy Status point.
D:
R:
Unoccupied
Unoccupied/Occupied
The following is a list of available points that you can use to set the alarm output to an alarm state if the alarm condition is
true. Set the alarm condition to
to turn this feature on for any individual alarm.
Equipment Alarm Lamp Initiators
CH-1 Linkage Failure Alarm
– Enables Chiller #1 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-2 Linkage Failure Alarm
– Enables Chiller #2 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-3 Linkage Failure Alarm
– Enables Chiller #3 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-4 Linkage Failure Alarm
– Enables Chiller #4 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-5 Linkage Failure Alarm
– Enables Chiller #5 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-6 Linkage Failure Alarm
– Enables Chiller #6 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-7 Linkage Failure Alarm
– Enables Chiller #7 Linkage failure alarm. D:
R:
Enable
Disable/Enable
CH-8 Linkage Failure Alarm
– Enables Chiller #8 Linkage failure alarm. D:
R:
Enable
Disable/Enable