Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
43
– The controller's occupancy status based on the local schedule. R: Unoccupied/Occupied
The current status of
when configured as a
contact input.
R: Inactive
Active Occupied
The
network input's current state. D:
R:
Unoccupied
Unoccupied/Occupied
Cooling Supply Setpoint Reset
– The
Chilled Water Supply Setpoint's
current reset
method.
Inactive
OAT Reset
RH Override
Demand Limit
– Based on outdoor air temperature, the amount of cooling
reset.
__°F
– Based on relative humidity, the amount of cooling reset that
will be subtracted from the
.
__°F
System Cooling Demand Level
– This unit's system cool demand level currently in effect.
0 to 3
– The current chiller plant's demand limit capacity received from an
external source.
0 to 100%
>
>
– Indicates if the unit is in a general equipment alarm. R: Normal/Alarm
– Indicates if the unit is in a Plant Power Failure alarm. R: Normal/Alarm
Leaving Load Water Temperature –
Indicates if the leaving load water temperature
exceeds the high or low limits.
R: Normal/Alarm
Entering Load Water Temperature –
Indicates if the entering load water temperature
exceeds the high or low limits.
R: Normal/Alarm
– Indicates an alarm if the outdoor air temperature falls
exceeds the high or low alarm limits.
R: Normal/Alarm