Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
43
Point Name/Description
Range
Schedules
The controller's occupancy status based on the local schedule. R: Unoccupied/Occupied
Occupancy Contact
The current status of
Input Channel #5
when configured as a
Remote Occupancy
contact input.
R: Inactive
Active Occupied
Global Occupancy
The
System Occupancy
network input's current state. D:
R:
Unoccupied
Unoccupied/Occupied
Reset
Cooling Supply Setpoint Reset
The
Chilled Water Supply Setpoint's
current reset
method.
Inactive
OAT Reset
RH Override
Demand Limit
Calculated OA Clg Reset
Based on outdoor air temperature, the amount of cooling
reset.
__°F
Calculated RH Clg Reset
Based on relative humidity, the amount of cooling reset that
will be subtracted from the
Calculated OA Clg Reset
.
__°F
Demand Limit
System Cooling Demand Level
This unit's system cool demand level currently in effect.
0 to 3
Ext Demand Limit
The current chiller plant's demand limit capacity received from an
external source.
0 to 100%
Alarms
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Alarms
Point Name/Description
Range
Equipment Alarm
Indicates if the unit is in a general equipment alarm. R: Normal/Alarm
Plant Power Failure
Indicates if the unit is in a Plant Power Failure alarm. R: Normal/Alarm
Leaving Load Water Temperature
Indicates if the leaving load water temperature
exceeds the high or low limits.
R: Normal/Alarm
Entering Load Water Temperature
Indicates if the entering load water temperature
exceeds the high or low limits.
R: Normal/Alarm
Outdoor Air Temperature
Indicates an alarm if the outdoor air temperature falls
exceeds the high or low alarm limits.
R: Normal/Alarm