Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
40
Lvg Load Water Temp Alarm
– Enables leaving load water temperature failure alarm. D:
R:
Enable
Disable/Enable
Lvg Load Wtr Sensor Alarm
– Enables leaving load water temperature alarm. D:
R:
Enable
Disable/Enable
Ent Load Water Temp Alarm –
Enables entering load water temperature alarm. D:
R:
Enable
Disable/Enable
Ent Load Wtr Sensor Fail Alarm
– When set to
, any Entering Load Water Sensor
Failure Alarm indicated by the controller also initiates an
and
energizes the
binary output.
D:
R:
Enable
Disable/Enable
– When set to
, any Outdoor Air Temperature Alarm
indicated by the controller also initiates an
and energizes the
binary output.
D:
R:
Enable
Disable/Enable
– When set to
, an Outdoor Air Temperature Sensor
Failure Alarm indicated by the controller also initiates an
and
energizes the
binary output.
D:
R:
Enable
Disable/Enable
– When set to
, a High Space Relative Humidity Alarm indicated by
the controller also initiates an
and energizes the
binary
output.
D:
R:
Enable
Disable/Enable
– When set to
, a Relative Humidity Sensor Failure Alarm
indicated by the controller also initiates an
and energizes the
binary output.
D:
R:
Enable
Disable/Enable
Properties > Control Program > Maintenance
– The type of equipment that the controller is controlling. R: Air
Water
– Displays the point used to control this equipment. R: Leaving Water Temp
Entering Water Temp
- Indicates whether chillers are equal or unequal size. R: Equal
Unequal
– The external demand limit input status. R: Off/On
– The total number of chillers in the chiller plant. R: 0 to 8