Appendix C: 30MP Multi-chiller Points/Properties
30MP Multi-chiller CARRIER CORPORATION ©2018
Installation and Start-up Guide All rights reserved
46
AI Setpoint
The current voltage of the controller's external chilled water setpoint
sensor input. Allowable input range is 1-5 Vdc.
R: 0 to 5 Vdc
OAT Sensor
The value of the controller's outdoor air temperature sensor input, prior to
any operator-configured
Calibration Offset
.
R: -56 to 245°F
Leaving Chilled Water Header Temp
The value of the controller’s leaving chilled water
header temperature sensor input, prior to any operator-configured
Calibration Offset
.
R: -56 to 245°F
Ext Demand Limit
The external demand limit input's current state. R: Off/On
Remote Occupancy Contact
The remote occupancy contact input's current state. R: Open/Closed
Tower Fan Speed
The assigned output channel's current commanded, configuration-
dependent, fan output.
R: 0 to 100%
Alarm Lamp
The assigned output channel's current commanded, configuration-
dependent, output.
R: Off/On