SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
157 OF 168
157
36
vssv_dly
0 to 10
5
min
Vapor Source SV Delay
37
evap_t_o
DSABLE_ENABLE
ENABLE
-
Evap Liquid Temp Opt
38
evap_ref
0 to 1
1
-
Evap App Calc Selection
39
blank
-
-
-
Sat Temp=0, Ref Temp=1
*Depends on the selected language (English by default).
CONFOPT2 - Option 2
Name
Range
Default
Unit
Displayed text*
1
iob3_opt
NO_YES
NO
-
IOB3 Option
2
iob4_opt
NO_YES
NO
-
IOB4 Option
3
freecool
NO_YES
NO
-
Free Cooling Option
4
blank
-
-
-
5
wp_opt
0 to 2
0
-
Water Pressure Option
6
blank
-
-
-
No=0,
7
blank
-
-
-
WTR Flow PD TRD=1,
8
blank
-
-
-
WTR Flow PD TRM=2
9
wfm_opt
0 to 3
0
-
Water Flow Measurement
10
blank
-
-
-
No=0,
11
blank
-
-
-
WTR Flow MTR=1,
12
blank
-
-
-
WTR Flow PD=2
13
fs_opt
0 to 2
0
-
Water Flow Determination
14
blank
-
-
-
Sat Temp=0,Flow Switch=1
15
blank
-
-
-
WTR Flow PD=2
16
flow4ma
0.00 to 45,420.00
0 to 12000
0.00
0
l/min
GPM
Water Flow at 4mA
17
flow20ma
0.00 to 45,420.00
0.00
l/min
Water Flow at 20mA