0 to 12000
0
GPM
18
chwf_bas
0.00 to 34,065.00
0 to 9000
0.00
0
l/min
GPM
Evap Flow Rate Baseline
19
evpd_bas
0.00 to 137.90
0 to 20
0.00
0
kPa
PSI
Evap Pres Drop Baseline
20
cdwf_bas
0.00 to 34,065.00
0 to 9000
0.00
0
l/min
GPM
Cond Flow Rate Baseline
21
cdpd_bas
0.00 to 137.90
0 to 20
0.00
0
kPa
PSI
Cond Pres Drop Baseline
22
wpd_20ma
68.95 to 275.80
10 to 40
68.95
10
kPa
PSI
Water Pres Drop @20mA
23
blank
-
-
-
24
mrn_opt
DSABLE_ENABLE
DSABLE
-
Marine Option
25
mrn_pt
DSABLE_ENABLE
DSABLE
-
Marine Transducer Option
26
pr_opt
DSABLE_ENABLE
DSABLE
-
Marine Pwr Req Option
27
cpr_opt
DSABLE_ENABLE
DSABLE
-
Marine Cont. Pwr Req
28
cfa_opt
DSABLE_ENABLE
DSABLE
-
Condenser Flush Alert
*Depends on the selected language (English by default).
CFGUMVFD - VFD Parameters
Name
Range
Default
Unit
Displayed text*
1
comp_hz
47 to 200
50
Hz
Compressor Speed 100%
2
rlv_i
200 to 13800
460
V
Rated Line Voltage
3
rla
10 to 2000
200
A
Motor Nameplate Current
4
rla_load
10 to 2000
200
A
Motor Rated Load Current
5
rlv
200 to 13800
460
V
Motor Nameplate Voltage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier SmartVu control and is the answer not in the manual?

Carrier SmartVu control Specifications

General IconGeneral
BrandCarrier
ModelSmartVu control
CategoryControl Panel
LanguageEnglish

Related product manuals