SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
160 OF 168
160
2
strt_dly
4 to 45
15
min
Start to Start Delay
3
dem_sel
0 to 1
0
-
Demand Limit Type
4
blank
-
-
-
Base Demand=0, 4-20mA=1
5
rampslct
0 to 1
1
-
Pulldown Ramp Type
6
blank
-
-
-
Temp=0, Load=1
7
DEM_SLCT
0 to 1
0
-
Demand Limit Source
8
blank
-
-
-
Amps=0, KW=1
*Depends on the selected language (English by default).
CFG_19DV - 19DV
Name
Range
Default
Unit
Displayed text*
1
sen_opt
0 to 3
0
-
Pressure Sensor Type
2
blank
-
-
-
Tianmu=0, Texas=1
3
blank
-
-
-
Sensata=2
4
pg_opt
DSABLE_ENABLE
DSABLE
-
Purge System Option
5
pgt_set
-1.11 to 148.89
30 to 300
18.33
65
°C
°F
Purge Active Temp SP
6
pgon_opt
DSABLE_ENABLE
DSABLE
-
Purge on Idle Option
7
reg_tim
-
120
min
Purge Regen Lasting Time
8
dis_temp
-17.78 to -9.44
0 to 15
-15.56
4
°C
°F
Purge Discharge Temp
9
dra_temp
-15.00 to -6.67
5 to 20
-11.11
12
°C
°F
Purge Drainage Temp
10
dis_time
5 to 20
5
sec
Purge Discharge Time
11
dly_time
10 to 40
30
sec
PG Discharge Delay Time