Pressures Menu – PRESSURE
No. Name Status Unit Displayed text* Description
1 DP_A - kPa Discharge Pressure A Discharge pressure, circuit A
2 SP_A - kPa Main Suction Pressure A Main suction pressure, circuit A
3 OP_A - kPa Oil Pressure A Oil pressure, circuit A
4 DOP_A - kPa Oil Pressure DierenceA Oil pressure dierence, circuit A
5 ECON_P_A - kPa Economizer Pressure A Economizer pressure, circuit A
6 DP_B - kPa Discharge Pressure B Discharge pressure, circuit B
7 SP_B - kPa Main Suction Pressure B Main suction pressure, circuit B
8 OP_B - kPa Oil Pressure B Oil pressure, circuit B
9 DOP_B - kPa Oil Pressure DierenceB Oil pressure dierence, circuit B
10 ECON_P_B - kPa Economizer Pressure B Economizer pressure, circuit B
11 DP_C - kPa Discharge Pressure C Not applicable to this unit
12 SP_C - kPa Main Suction Pressure C Not applicable to this unit
13 OP_C - kPa Oil Pressure C Not applicable to this unit
14 DOP_C - kPa Oil Pressure DierenceC Not applicable to this unit
15 ECON_P_C - kPa Economizer Pressure C Not applicable to this unit
*Depends on the selected language (English by default).
Inputs Menu – INPUTS
No. Name Status Unit Displayed text* Description
1 ONOFF_SW open/close - Remote On/O Switch Remote on/o switch
2 HC_SW open/close - Remote HeatCool Switch Remote heating/cooling selection switch
3 SETP_SW open/close - Remote Setpoint Switch Remote setpoint selection switch
4 LIM_SW1 open/close - Limit Switch 1 Demand limit switch 1
5 LIM_SW2 open/close - Limit Switch 2 Demand limit switch 2 (EMM option)
6 OIL_L_A open/close - Oil Level Input A Oil level input, circuit A
7 OIL_L_B open/close - Oil Level Input B Oil level input, circuit B
8 OIL_L_C open/close - Oil Level Input C Not applicable to this unit
9 CURREN_A - A Motor Current A Motor current, circuit A
10 CURREN_B - A Motor Current B Motor current, circuit B
11 CURREN_C - A Motor Current C Not applicable to this unit
12 SP_RESET - mA Reset/Setpnt4-20mA Sgnl 4-20 mA signal, setpoint reset
13 REM_LOCK open/close - Customer Interlock Customer interlock: When the contact is closed, the unit
will be stopped with no delay. The switch is provided on
the customer's terminal block of the optional EMM.
14 ICE_SW open/close - Ice Done Storage Switch Ice storage end switch
15 OCC_OVSW open/close - Occupied Override Switch Occupied override switch
16 LIM_ANAL - mA Limit 4-20mA Signal 4-20 mA signal, capacity limit
17 ELEC_BOX open/close - Electrical Box Interlock Electrical box interlock
18 bacdongl no/yes - BACnet Dongle BACnet dongle: Used when the unit is incorporated
into the BACnet network
19 leak_v - V Leakage detector 1 val Refrigerant leakage detection (optional)
20 leak_2_v - V Leakage detector 2 val Refrigerant leakage detection (optional)
21 ElBxF1_s o/on - Electrical Box Fan status 1 Electrical box fan status
*Depends on the selected language (English by default).