NVF5 Series User Manual Appendix B Parameter list
(0.001 ~ 65.535)mH(Inverter
Power > 55kW)
F2.10
Motor Mutual
inductance
(0.1 ~ 6553.5)mH(Inverter
Power <= 55kW)
(0.01 ~ 655.35)mH(Inverter
Power > 55kW)
Depend on
motor type
F2.11
Motor no-load
current
0.01A ~ F2.03(Inverter Power
<= 55kW)
0.1A ~ F2.03(Inverter Power >
55kW)
Depend on
motor type
F2.22 Motor Auto Tuning
0:No Operation
1:Static Tune
2:Rotate Tune
0
F3 Motor Vector Control Group
F3.00
Speed/Torque
Selection
0:Speed Regulation
1:Torque Regulation
0
F3.01
(
ASR1-P)
1 ~ 100
30
○
F3.02
(Low Speed ASR1-I)
( 0.01 ~ 10.00 ) s
0.50s
○
F3.03 Switch Frequency1
0 ~ F3.06
5.00Hz
F3.04
(
ASR2-P)
1 ~ 100
20
○
F3.05
(Low Speed ASR2-I)
( 0.01 ~ 10.00 ) s
1.00s
○
F3.06 Switch Frequency 2
F3.03 ~
Max. Output
Frequency F0.07
10.00Hz
○
F3.07
Rate in Vector Control
( 50 ~ 200 ) %
100%
○
F3.08
(0.000~0.100)s
0.000s
○
F3.09
Torque Upper Limit
Value of the Speed
Loop
( 0.0 ~ 300.0 ) %
180.0%
○
F3.10
Braking Torque Upper
Limit Value of the
Speed Loo
( 0.0 ~ 300.0 )%
180.0%
○
F3.11 Flux Regulation Kp
0 ~ 60000
2000
F3.12 Flux Regulation Ki
0 ~ 60000
1300
F3.13 Torque Regulation Kp
0 ~ 60000
2000
- 116 -