NVF5 Series User Manual Appendix B Parameter list
Code
Name
Setting Range
Default
Change
F8.23
Output Current Over
Limit Detection Delay
Time
0.00~600.00s
0.00s
F8.24
Current Reach
Detection Value 1
0.0~300.0%
100.0%
F8.25
Current Reach
Detection Value 1
Level
0.0~300.0%
0.0%
F8.26
Current Reach
Detection Value 2
0.0~300.0%
100.0%
F8.27
Current Reach
Detection Value 2
Level
0.0~300.0%
0.0%
F8.28
Power Moudle
Temperature Reach
0~100
75
F8.29
Cooling Fan
Automaticlly Control
0Running in Auto Mode
1Fan Running in Power
0
F8.30 Droop Control
0.00 10.00Hz0.00Hz
Ineffective
0.00Hz
F8.31
Start Protection
Selection
0No Applicable
1Start Protection
1
F8.32 Timer Function
0Ineffective
1Effective
0
F8.33 Timer Running Timer
0.0 6500.0min
0.0min
F8.34
Current Running
Reach Time
0.0 6500.0min
0.0min
F8.35 Auto Restart Function
0Ineffective
1Effective
0
F8.36
Auto Restart Delay
Time
0.0 10.0s
0.0s
F8.37 Sleep-Wake Function
0Ineffective
1Effective
0
F8.38 Sleep Frequency
0.00 Hz F0.07
0.00Hz
F8.39 Sleep Dealy 0.0s ~ 6500.0s 0.0s
F8.40 Wake Level
0.0 100.0%
0.0%
F8.41 Wake Delay
0.0 ~ 6500.0s
0.0s
F9 Process PID Control Group
F9.00
PID Reference
Selection
0Digital Given
1AI1
2AI2
3Reserve
4HDI
5Reserve
6Preset Speed
1
- 128 -

Table of Contents

Other manuals for CHINT NVF5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CHINT NVF5 Series and is the answer not in the manual?

CHINT NVF5 Series Specifications

General IconGeneral
BrandCHINT
ModelNVF5 Series
CategoryInverter
LanguageEnglish

Related product manuals