NVF5 Series User Manual Appendix B Parameter list
F9.01 Feedback Selection
0:AI1
1:AI2
2:Reserve
3:AI1+AI2
4:AI1-AI2
5:MIN(AI1,AI2)
6:MAX(AI1,AI2)
7: HDI
8:Reserve
1
F9.02
Reference Digital
Given Setting
( 0.0 ~ 100.0)%
50.0%
○
F9.03 KP
0.0 ~ 100.0
20.0
F9.04 Ki
0.01 ~ 10.00
2.00
F9.05 Kd
0.000 ~ 10.000
0.000
F9.06 Sampling Period
(0.01 ~ 50.00)s
0.50s
F9.07
(0.00 ~ 650.00)s
0.00s
○
F9.08 Feedback Filter Time
(0.00 ~ 60.00)s
0.00s
F9.09 PID Output Filter Time
(0.00 ~ 60.00)s
0.00s
F9.10 Offset Limit
(0.0 ~ 100.0)%
0.0%
F9.11 Differential limiting
(0.00 ~ 100.00)%
0.10%
F9.12
The Max. Positive
Offset between the
Two Outputs
(0.00 ~ 100.00)%
1.00%
○
F9.13
Offset between the
(0.00 ~ 100.00)%
1.00%
○
F9.14
Invert Selection
0 :
Close Loop Output is
Negative,Inverter Run in
Lower Limit Frequency
1 :
Close Loop Output is
Negative,Inverter Run Reverse
0
○
F9.15 Close Loop Adjust
0:Positive Direction
1:Negative Direction
0
F9.16
Selection
0:Ineffective
1:Effective
Ones Place:
When Frequency
Limit,Integral Stop
Tens Place:When Frequency
Reach Upper/Lower
Limit,Integral Continue
0x0000
○
F9.17 Kp2 0.0 ~ 100.0 20.0