NVF5 Series User Manual Appendix B Parameter list
Code
Name
Setting Range
Default
Change
Fd .38
Fan Running Elapsed
Time
0 ~ Max.65535Hours
0
●
Fd .39 Rated Capacity
(0 ~ 999.9)kVA(Depend On
Series)
Set By
Factory
●
Fd .40 Rated Voltage
(0 ~ 999) V (Depend On
Series)
Set By
Factory
●
Fd .41 Rated Current
(0 ~ 999.9)A(Depend On
Series)
Set By
Factory
●
Fd.42 Serial Type Range:0x0000~0xFFFF 0x0500
●
Fd .43 Software Version
0.00 ~ 99.99
1.00
●
Fd .44 Customized Version
0 ~ 99.99
1.00
●
Fd .45
Source Code
Compilation Year
2014 ~ 2099
2017
●
Fd .46
Source Code
Compilation Date
101 ~ 1231
101
●
Fd.47 Setting RPM
(0 ~ 60000)rpm
0
●
Fd .48 Current Running Time
(1 ~ 65535)min
0
●
Fd .49 Rest Running Time
(0 ~ 65535)H
0
●
Fd .50 Power Factor Angle 0.1 ~ 20.0 0
●
Fd .51
VF
Separated Target
Voltage
(0.0 ~ 100.0)%(Motor Rated
Voltage)
0.0%
●
Fd .52
VF Separated Output
Voltage
(0.0 ~ 100.0)%(Motor Rated
Voltage)
0.0%
●
Fd .53
Inverter GP Type 0 ~ 3 0
●
Fd .54 Motor Temperature
(1~200)℃
0℃
●
FE Protection and Early Alarm Group
FE.00
Motor Overload
Protection Selection
0:Ineffective
1:Effective
1
○
FE.01
Motor Overvoload
Protection Gain
0.20 ~ 10.00
1.00
○
FE.02
Motor Overload Early
Alarm Enable
0:Ineffective
1:Effective
0
○
FE.03
Motor Overload Early
Alarm Level
(20 ~ 200)%
80%
○
FE.04
Overvoltage Stall
Protection Selection
0:Ineffective
1:Effective
2:Effective in Decel.Mode
0
○
FE.05 Overvoltage Stall Gain
0 ~ 100(0:Prohibit)
0
○
FE.06
Overvoltage Stall
Protection Voltage
(120 ~ 150)%
130%
○
FE.07 Overcurrent Stall Gain
0 ~ 100(0:Prohibit)
20
○
FE.08
Overcurrent Stall
(100 ~ 200)%
150%
○
- 136 -