NVF5 Series User Manual Appendix B Parameter list
FE.09
Protection Selection
0:Ineffective
1:Effective
1
○
FE.13
Off Action Selection
0:Ineffective
1:Deceleration
2:Decel. Stop
0
○
FE.14
Judgement Voltage of
Instantaneous Action
(80.0 ~ 100.0)%
90.0%
○
FE.15
Judgement Time of
Instantaneous Power
Failure Voltage Rise
(0.00 ~ 100.00)s
0.50s
○
FE.16
Judgement Voltage of
Instantaneous Power
Failure
(60.0 ~ 100.0)%(Standard
DC Bus Voltage)
80.0%
○
FE.17
Load Loss Protection
Selection
0:Ineffective
1:Effective
1
○
FE.18
Load Loss Detection
Level
( 0.0 ~ 100.0)%
10.0%
○
FE.19
(0.0 ~ 60.0)s
1.0s
○
FE.20
Value
(0.0 ~ 50.0)%(Max. Output
Frequency)
20.0%
○
FE.21
Time
( 0.0 ~ 60.0 ) s ( 0.0s No
Detection)
1.0s
○
FE.22
Detection Value of
Excessive Speed
Deviation
(0.0 ~ 50.0)%(Max. Output
Frequency)
20.0%
○
FE.23
Detec When
Excessive Speed
Deviation
( 0.0 ~ 60.0 ) s ( 0.0s No
Detection)
5.0s
○
FE.24
Detection Selection
0:Input Phase Loss Hardware
Detection
1: Input Phase Loss Software
Detection
2 :
No Input Phase Loss
Hardware/Software Detection
1
FE.25
Detection Selection
0 :
Software Detection
1:Output Phase Loss Software
1
FE.26
Automaticlly Reset
Fault Times
0 ~ 20
0
○
FE.27
Automaticlly Reset
Fault Inerval
(0.1 ~ 100.0)s
1.0s
○
FE.28
Fault Do Action When
Automaticlly Reset
Fault
0:Fault lockout prohibited
1:Fault lockout permit
0
○
FE.29 Fault Log 1
0~55
0
- 137 -